Operation control of GRH3 air compressor

Monday - 29/07/2019 04:19
1.Operation Control.
Turn on
If it is turned on with the MCB on inside the control box, the controller’s main LCD is activated.
Micom is self-checked and is readily stand-by for operation.

Main Display .
                                                      
                                                     
 

Line 1: discharge pressure .
Line 2: discharge temperature .
Line 3: total operation hours .
Line 4: date(YY.MM.DD HH:MM .

If any fault is found in a compressor after turning on Micom, it displays alarm and trip; or, it shows the above display.
2. Operation Stop.
2.1 To start the operation, press [START] button. Then, [START] lamp is on in red.
2.2 To stop the operation, press [STOP] button. Then, [STOP] lamp is on in green mode.
For schedule operation, press [SCHEDULE] button once to select the schedule  
If pressing [START] button after selecting the schedule mode, a compressor operates and stops in accordance with the pre-defined schedule operation time.
To suspend it during operation, press [STOP] button.
3. Remote Operation.
A compressor can be remotely controlled. To control the operation or stop, wire the Start and Stop buttons in TR2 of the electrical box as presented in the figure below. For the details, refer to page 40.

<Remote Operation/Stop>
Basically, the operation/stop control and operating status are configured to be remotely outputted by the contact.

Procedures.
1) Operation and Stop buttons should be connected respectively as seen in the above figure.
2) A compressor starts operating if pressing ‘Remote Operation’ button once.

3) If pressing ‘Remote Stop’ button once, a compressor stops after no-load operation for 10 seconds.
4) To remotely check whether a compressor is operating or stops, please use ‘remote signal output’ terminal.
4. Remotely Controlling Load/No-load Operation.
1) To remotely control load/no-load operation of a compressor, connect the switch as presented in the above TB2.
2) No load operation: no load operation is allowed if connecting +24 terminal to 104 terminal.
3) Load operation: load operation is allowed if +24 terminal is not connected to 104 terminal.

* The operation/stop can be controlled by Micom’s controller even during remote operation.



 